| Civil Defense Now! Blast and Fire Resistance
By Richard A. Fleetwood - May 2001
The information on this page provides data to help protect your homes and belongings from some of the direct effects of nuclear weapons, namely blast waves and thermal ignition. The data below was scanned in and converted originally by Robin Hanus, and the zip file of it can be found on my SHELTER PLANS page, as well as Robin's website at www.bwolf.com. Thanks, Robin.
Increasing Blast and Fire Resistance in Buildings:
Design Techniques for Combined Nuclear Weapon
Effects
Department of Defense, Defense Civil Preparedness Agency
TR-62, May 1976
(Supersedes TR62, dated December 1970, which maybe
used)
Preface
In a nuclear attack against the United States, people
very close to an explosion-in the area of total destruction-would be
killed by blast or by extreme heat of the nuclear fireball. People just out-side this
area-in the area of heavy destruction-would be severely affected by blast,
heat, initial nuclear radiation, fallout radiation and fires. People in the fringe
area would be subjected to lesser blast, heat and fire hazards. People outside the
fringe area would not be affected by the blast, heat or fires. To them and to the
survivors closer to the point of explosion (ground zero) radioactive fallout might be the
main danger.
Rational design can enhance man's chances of surviving the hostile
environment created by a nuclear explosion. Just as design in some areas takes into
account the effects of earthquakes, hurricanes, tornadoes or extreme snowloads, so also
may it take into account protection from some of the effects of nuclear weapons. This does
not mean the design and construction of special shelter facilities but simply the
application of appropriate design techniques to ordinary buildings. Some degree of
protection can be achieved without compromising
the primary function of the building or adversely affecting
appearance or cost. Protected areas need not be recognizable as shelters.
Basic concepts of design techniques for increasing protection
against blast and fire effects are given here. Publications presenting additional
information on design to resist nuclear weapons effects are listed in the selected
references. Detailed design procedures, and the determination of the degree of overall
protection, are left to competent consultants.

Introduction
While many buildings afford a degree of protection against fallout
radiation-some being better than others-they are vulnerable to thermal and blast effects
of nuclear weapons. Most of the United States would not be affected by blast, heat or
fires in the event of a nuclear attack. But a sizeable portion of our population would
be threatened by the direct effects of nuclear explosions. Their survivability can be
enhanced by design techniques in new construction to give some protection against these
hazards. To explain some of the basic concepts involved, it is necessary to review briefly
the environment created by nuclear explosions, the potential hazards, and the response of
buildings and their inhabitants to the environment.
The Influence Of Nuclear Explosions On Building Design
Thermal radiation and prompt nuclear radiation are the first effects
to threaten areas relatively close to a nuclear explosion. When thermal radiation strikes
an object, much of the energy is absorbed. The amount absorbed determines whether
combustible materials will be ignited or whether people will be burned. Thin, highly
combustible materials such as paper, window curtains, leaves and dry grass can easily be
ignited. They act as kindling for heavier combustible building materials, which fuel major
fires.

Intense initial radiation is experienced at locations near the
explosion during the first minute after detonation. The effect of this prompt or initial
radiation on people and the protective measures to be taken are somewhat different from
those for fallout radiation. However, initial nuclear radiation from weapons in the
megaton range is not a serious threat beyond the area of heavy destruction.
The effects of the shock wave, which travels away from the explosion
faster than the speed of sound, poses the next hazard at close-in locations. The shock
front is similar to a moving wall of highly compressed air and is accompanied by blast
winds. When it arrives at a location, it causes a sudden rise in the ambient pressure. The
increase in atmospheric pressure over normal values is referred to as overpressure, and
the simultaneous pressures created by the blast winds are called dynamic pressures. Both
decay rapidly with time from their peak values to ambient pressure and overpressure
actually sinks below ambient before equalizing back to normal atmospheric pressure.
Blast pressures can create loads on buildings that are many times
greater than normal design loads, and blast winds can be much more severe than hurricanes.
Buildings with relatively weak curtain walls and interior partitions would probably be gutted
very early during the blast phase, even at low overpressures. Dynamic pressures would
then continue to cause drag loads on the structural frame that is left standing. Slabs
over closed basements would experience the downward thrust of the over-pressure, which
would be transmitted to supporting beams, girders and columns. Foundations would
experience blast-induced vertical and overturning forces. Failure would occur unless the
structural system was designed to resist these large, quickly applied loads.
Structures with load-bearing walls or curtain walls that do not blow
out easily could be completely demolished or toppled by blast loads. Such structures would
experience the combined loading conditions caused by the incident overpressure, the
dynamic and highly transient reflected pressures that develop when the shock wave strikes
a surface of the structure.
People in basement shelters who are protected against catastrophic
structural collapse, high pressures and flying objects would have the greatest probability
of surviving the blast phase.
The air blast can penetrate basement areas that are open to the
atmosphere causing internal pressures to build up and creating high-velocity jets of air
through the openings. Shattered window glass and other objects become dangerous missiles
in the air jets. High internal pressures can cause lung damage and eardrum rupture. The
air jets, under certain circumstances, can pick people up and hurl them against fixed
objects, possibly with lethal effects.
Secondary fires triggered by blast damage such as broken utility
lines, overturned appliances, electrical short circuits, etc., present additional hazards
to the survivors of the blast and thermal phases of the attack. Flammable building
materials, furniture and debris created by the blast can provide the fuel to support
fires.
Radioactive fallout particles may drift hundreds of miles from the
explosion (ground zero) before falling back to earth. Although higher radiation doses, in
most cases, are experienced in the closer in regions, virtually any portion of the United
States may be subjected to a potentially lethal dose of radioactivity in the event of a
nuclear attack. Information on radioactive fallout, the effects of gamma radiation and
fallout radiation shielding are given in detail in other referenced DCPA publications.

The Plan For Survival
The combination of the thermal pulse and major superstructure blast
damage leaves little chance for survival for people in upper stories of buildings within
the area of heavy destruction. Basements generally offer the best protection against these
hazards and are best suited to protect against the hazards of secondary fires and fallout
radiation. Surveys have shown that, while basements are potentially less vulnerable, weak
points in their design drastically reduce the probability of survival at close-in
locations. If these weak points can be avoided during the design stage, significant
protection can be achieved at modest cost against the combined effects of nuclear weapons
outside and to some extent within the area of heavy destruction.
Principles of Protective Design
Balanced protection from the combined hazards of nuclear explosions
may be achieved in the basement of buildings by considering the influence of thermal
radiation, fires and blast on design.
Thermal Radiation
Thermal radiation travels in a straight line from its source-the nuclear fireball-until it
interacts with matter. Any solid, opaque materials will shield against thermal energy.
Combustible materials will ignite when the thermal energy they absorb reaches the ignition
threshold. Light colors and shiny surfaces will reflect a great deal of thermal radiation;
dark, dull surfaces will absorb most of the thermal radiation that strikes them. A thin
material is more likely to ignite than a thick material, since there is little opportunity
for heat to be conducted away from surface layers. Protection against primary ignitions
can be achieved by limiting the radiant heat energy that can penetrate the building.
Metallic blinds or glass fiber draperies over windows will shield
combustible furnishings from the thermal pulse. Blinds painted in light colors and having
noncombustible tapes will afford protection even though the paint may char. Although
transparent materials cannot provide a complete shield against thermal radiation, solar
glass will reduce the thermal energy reaching the interior of the room more than ordinary
window glass and will have performed this function efficiently before the blast. Avoid
combustible draperies and window shades.
As a minimum, shielding against thermal radiation should be provided
on the first floor of the building. Since the buildup of fires requires at least several
minutes, shelter occupancy plans should also include provisions for fire teams to
extinguish early fires.

Fires
Primary fires are ignited by the thermal pulse, and secondary fires
result from blast damage. These fires then spread to involve other combustible objects and
buildings. Regardless of how a fire starts, how much it develops and spreads depends on
the amount and distribution of combustible material in the vicinity. Burning buildings
produce radiant heat that behaves like the radiant energy of the thermal pulse. Windows
and combustible materials increase the amount of radiant heat transmitted from a burning
building. The heat intensity reaching an adjacent building depends on the distance between
the buildings. Thermal protection devices over windows would be blown away by the blast
wave just after the thermal pulse. The building would then be exposed to ignition by the
thermal radiation and burning material from adjacent buildings.
Perhaps least known is the nature of the fire problem in a
severe-blast-damaged zone. Survival expectancy may be improved in many instances in which
blast removes the combustible materials in the aboveground space. The following
observations on the behavior of heat and gases generated by fires influence the location
and design of-a shelter:
(1) Although convection heat currents rise, some heat can be
conducted through slabs and walls surrounding the fire. (2) Dangerous oxygen depletion and
lethal carbon dioxide buildup may occur at elevations equal to or higher than the active
fire zone but generally not in areas below the fire. (3) Smoke containing carbon monoxide
and other toxic gases may drift or be blown into the areas below the fire, although
limited experimental data indicate that this may not be a serious hazard for basement
occupants.
Providing a cleared area around a building is the best way to
prevent fire spreading. The building should be sited to provide the maximum separation
from adjacent buildings. The greatest fire threat is posed by a building with large
openings, combustible exterior walls and large quantities of stored combustibles. Ignition
of the roof by heat radiation from taller buildings can be minimized if the exposed roof
is Class A or B as defined by the National Fire Code. Fire-resistant exterior walls will
protect the building from ignition and, if the building walls are demolished by the blast
wave, the amount of combustible rubble in and around the building will be reduced. The
window area and openings on the walls facing potential fire hazards should be minimized.
If the appropriate separation distance cannot be achieved, there should be a three-hour
firewall between the buildings. (Refer to local code requirements.) Fire spread seldom
occurs when buildings are separated by distances of 60 feet or more.
Spreading of a fire that may get into the building above a shelter
can be limited by reducing the combustible content or by use of fire resistant or fire
retardent treated furnishings. Since building use generally governs the fire load, uses
that produce the least combustible furnishings and equipment should be planned for areas
above or near the shelter. If the first-floor slab is the shelter ceiling, particular care
should be taken in selecting furnishings and wall coverings and in locating utilities and
equipment so the first story will not be exposed to a rubble fire. Shelter walls and roofs
that may be exposed to fires can be insulated to reduce heat flow into protected areas.
The use of incombustible materials will help to keep fires from spreading from floor to
floor.
For protection against fires occurring in non-shelter portions of
the basement, an airtight exhaust system should be designed to move air in the direction
of the non-shelter area. It is likely that, of the usual scattered sources of inlet air,
some will be useable for ventilation. If portable ventilation equipment is used, it should
be placed so as to pull in air from openings where fresh air is available and exhaust it
through other openings. An independent emergency ventilation system designed to provide a
positive pressure in the shelter area of one-quarter to one-half inch of water is a good
way of keeping out smoke and poisonous gases. To fight infiltration, pipes and ducts that
penetrate the shelter walls and ceilings should be grouted or equipped with sealants or
gland seals wherever possible. Vapor-tight fire dampers should be provided in ventilation
ducts that extend into the shelter area from the normal building ventilation system.
Automatic heat-fused dampers must be capable of being operated manually from within the
shelter.

Summary
Thermal protection devices over windows and openings will shield the
interior of buildings from the thermal pulse but would probably be blown away by the
subsequent blast. The combustible contents of buildings should be kept to a minimum to
prevent fires from starting and spreading. The building should be sited to provide maximum
separation from adjacent buildings. Incombustible roofs, exterior walls and fire protected
structural systems will reduce the threat of ignition from adjacent burning buildings.
Provisions should be made to keep smoke and poisonous gases from penetrating the shelter
area.
Blast
As the blast wave engulfs a building, it produces large pressures on
exposed surfaces and penetrates to the inside through openings. The overpressure causes
hydrostatic-type loads, and the dynamic pressure causes drag or wind type loads. High
reflected pressures are generated on surfaces that the shock front strikes head-on or
nearly head-on. At a given distance from ground zero, overpressures and dynamic pressures
decay with time but may last for several seconds. The time it takes the reflected
pressures to clear a point on a surface depends mainly on the distance to a free edge or
an opening and may be one-tenth to one-hundredth of a second. Due to their sudden
application and relatively long duration, loads produced by overpressure and dynamic
pressure can be more critical than equivalent static loads, but the damaging effects
of the even higher reflected pressures are reduced by their short life. A building with
very frangible walls (i.e., walls that are very readily demolished by the air blast) will
be rapidly reduced to a bare frame that will experience mostly drag forces. Stronger
exterior walls and shear walls will cause the structure to be loaded with reflected
pressures, overpressures and dynamic pressures that could cause severe damage or even
total collapse.

Frangible upper-story walls and partitions will give way rapidly
when struck by the blast, permitting overpressures to equalize quickly around columns and
beams and over and below exposed slabs. Consequently, the high reflected pressures will
decay so rapidly that the structure will receive little impulse, and the loading on the
almost bare frame will be essentially the drag loading associated with the dynamic
pressure. The frame and slabs of a frangible-wall structure would probably be left
standing with rubble on the slab and around the building. The stronger the exterior walls,
the more total load will be imparted to the structural frame. To reduce the amount of
rubble on the slab over a basement shelter which has been designed to resist the combined
effects, the first-floor walls should be made as frangible as possible.
Slabs over sealed off spaces will be loaded mainly by the
overpressure that builds up as the shock front engulfs the building. Basement spaces with
openings will be penetrated by the blast pressures, but relief to the slab loading will be
negligible since it takes so long for the inside pressures to build up. Jets of air
rushing through the openings will exert large drag forces on objects in their paths,
although the jets are fairly restricted and short lived.
Blast protection may be achieved in basements through the
application of a few basic principles in the design. Design techniques that enhance the
strength and ductility of structural elements will increase resistance to blast loads.
Exposed basement walls will experience the full effect of the high
reflected pressures that develop when a shock wave strikes a vertical surface. If the
natural topography does not allow the basement to be wholly below grade, earth berms can
be used to protect the basement walls from reflected pressures. Otherwise, exposed shelter
walls must be designed to resist the reflected-pressure impulse, which will be reduced if
the walls of the story above the shelter are made frangible. Outside doors and stairways
are very vulnerable to blast loadings, and the openings that they leave can allow the
blast waves to penetrate the shelter space. Locating openings near the corners of the
building will reduce the duration of the reflected pressures on them.

The need for radiation shielding, tire resistance, strength and
ductility favors reinforced concrete as a construction material for floors.
Blast-resistant design philosophy allows structural elements to undergo large inelastic
(plastic) deformations in response to blast loading. Since blast loads act for a short
period of time, the most efficient structural system is one that absorbs the blast energy.
A ductile structure that undergoes large deformations without failure can absorb much more
energy than a brittle structure of the same static strength. Ductile response of
reinforced concrete structures to blast loads may be achieved by applying a few basic
principles in the structural design of the building.

In beams, slabs and other bending members, the relative amounts of
concrete and reinforcing steel should be proportioned so that the ductile steel will yield
before the more brittle concrete begins to crush. Such an under reinforced flexural member
will respond in a ductile manner to blast loads. If the section is over reinforced, the
concrete crushes before the tension steel yields, causing a brittle failure. Tensile
reinforcement between 0.5 and 2 percent of the cross-sectional area of the concrete
element will usually insure ductile behavior while providing the required strength.
Compression steel in flexural members serves two purposes. After a structural member is
deflected by blast loads, it attempts to spring back or rebound. Dynamic rebound causes
load reversal and, under certain circumstances, can result in catastrophic failure if
sufficient rebound resistance is not provided. Compression steel is used to provide the
required rebound strength. Compression steel also increases the ductility of the section
by inhibiting crushing of the concrete. Compression steel should not be less than 0.25
percent of the cross-sectional area. Ductile behavior of reinforced concrete will occur
only if the concrete is adequately confined by means of web reinforcement. Vertical web
steel is usually needed to prevent brittle diagonal tension failure. To insure ductile
behavior, the amount of diagonal tension reinforcement should be greater than 0.25
percent. Stirrups may be used to provide the required web reinforcement; stirrup ties will
aid in confining the concrete.
There is no advantage in using bent or truss-type bars, so all
flexural steel should be straight except for anchorage hooks. Brittle shear failure is
avoided in bending members if the section is deep enough for average shear stress on the
critical section to be not more than 20 percent of the compressive strength of the
concrete. Because blast loads are always much larger than dead loads, there is no
advantage to using prestressed concrete in blast-hardened beams and slabs. If prestressed
concrete is used, sufficient unpre-stressed mild steel should be added to assure ductile
response and to provide the required rebound resistance to blast loads.

Column concrete must be adequately confined by means of special
transverse reinforcement in areas where yielding will occur in rigid frame construction.
Complete continuity is essential for the structure to act efficiently as a unit in
absorbing blast energy. The resistance of a tied column will drop off sharply after its
limiting static strength is reached, but a spirally reinforced column (with the same area
of steel and concrete as the tied column) can undergo substantial deformations before
losing its ability to support a load. Since spiral columns are more ductile than tied
columns, they are more suitable in resisting blast loads. In view of the particular
seriousness of column failures, columns should always have a resistance at least equal to
the maximum resistance of the structural elements they support.
Flat-slab floors over the shelter area should have either a column
capital or drop panel or both. Flat plates (i.e., flat slabs without column capitals or
drop panels) have been shown to be very unsatisfactory in resisting blast loads. Brittle
shear failures around the columns can result in the slab punching through at the columns
and collapsing into the shelter area.
Summary
The use of frangible upper-story walls and partitions will reduce
the probability of a building being toppled or completely demolished by blast. Blast
resistant shelters should be below grade wherever possible. Exposed shelter walls and roof
slabs should be blast hardened. Ductile reinforced concrete can absorb the blast energy
while providing the needed fire and fallout protection. Under-reinforced flexural members
with adequate shear, bond and diagonal tension resistance will insure ductile response to
blast loads. Flat-plate construction should not be used over the shelter area.
Selected References
1. Effects of Nuclear Weapons, Department of
Defense and Atomic Energy Commission, 1962
edition (1964 reprinting) Superintendent of
Documents, Washington, D.C. 20402.
2. Feasibility Study of Slanting for Combined Nuclear Weapons
Effects, Stanford Research Institute, June 1969. This document is available from the
Clearing House for Federal, Scientific and Technical Information.
3. Design Structures to Resist Nuclear Weapons Effects, A.S.C.E.-Manual
of Engineering Practice-No. 42, 1964.
4. Technical Standards for Fallout Shelters, TM-
72-1, DCPA.
5. *Shelter Design and Analysis. Fallout Radiation Shielding, TR-20-(Vol.
1) DCPA.
6. *Shelter Design and Analysis, Protective Construction for
Shelters, TR-20-(Vol. 4), DCPA.
7. Design Modification Studies, TR-51, Office of Civil
Defense, April 1968.
8. Environmental Protection, TR-39, DCPA
*These publications are available only to architects and engineers who
are certified fallout shelter analysts.
Distribution List:
DCPA Regions, Staff college State CD Directors lnstructors
Qualified in Fallout Shelter Analysis C of E Field Officers Professional Societies
Interested in protective Construction
U. S. GOVERNMENT PRINTING OFFICE 1976 0 - 204-494
Provided for you by BlueWolf Productions at: http://www.bwolf.com
Updated May 2001 - © 2001 By Richard A. Fleetwood |